FUNGSI CT

1. MENTRANSFORMASIKAN ARUS YANG BESAR KE

YANG KECIL DIGUNAKAN UNTUK PENGUKURAN DAN PROTEKSI

2. SEBAGAI ISOLASI ANTARA SISI TEGANGAN YANG YANG DIUKUR / DIPROTEKSI DENGAN ALAT UKUR / PROTEKSINYA .

Page 3: Transformator Arus Current Transformator (Ct)

TEORI

P1 P2

S1 S2

MISAL RASIO CT500/ 5 A

a

1

I

N

I

I

NINI

2

2

2

1

2211

rmasian transfoperbanding a

sekunderbelitan Jumlah N

primerbelitan Jumlah N

sekunder ArusI

primer ArusI

2

1

2

1

Page 4: Transformator Arus Current Transformator (Ct)

PENGENAL TRAFO ARUS ( CT )

1. DUA PENGENAL PRIMER CONTOH 500 – 1000 / 5A

P1 P2

S1 S2

500A

5A

SAMBUNGAN SERI

P1 P2

S1 S2

1000A

5A

SAMBUNGAN PARALEL

Page 5: Transformator Arus Current Transformator (Ct)

2. MULTI RASIO CONTOH : 100 – 200 – 300 – 400 – 500 – 1000 – 1500 /5A

A B C D E F G H

P1 P2A – B 100 / 5AA – C 200 / 5AA – D 300 / 5AA – E 400 / 5AA – F 500 / 5AA – G 1000 / 5AA – H 1500 / 5A

Page 6: Transformator Arus Current Transformator (Ct)

3. MULTI CORE ( Inti besi lebih dari satu )

- DUA INTI CONTOH 1000 / 5 – 5A

P1

P2

1S1

1S2

2S1

2S2

5A

5A

- TIGA INTI CONTOH ( 1000 / 5 – 5 – 5A )

P1

P2

1S1

1S22S1

2S2

5A

5A

5A

3S2

3S1

1000A1000A

Masing masing dapat mempunyaiKelas dan burden yang sama atauBerbeda.

Page 7: Transformator Arus Current Transformator (Ct)

KELAS KETELITIAN

Dinyatakan dengan kesalahannya

1. KESALAHAN RASIO

P

PSN

I

).100II(KE%

sekunder ArusI

primer ArusI

asi transformRasioK

S

P

N

sekunder rated II )(

sekunder rated II ) (

S

S

2. KESALAHAN SUDUT

Pergeseran sudut sisi sekunder kurang atau lebih dari ( - ) lagging ( + ) leading

o180

Page 8: Transformator Arus Current Transformator (Ct)

3. COMPOSITE ERROR

dt)ii(KT

1

I

100e 2

PS

T

0 NP

gelombangsatu waktu lamaT

sekunder arussesaat nilaii

primer arussesaat nilaii

primer arus RMS nilaiI

asi transformrasio ratedK

S

p

P

N

Page 9: Transformator Arus Current Transformator (Ct)

CT UNTUK PROTEKSI

Pada arus pengenal

Kesalahan Kesalahan

Rasio sudut

Kesalahan komposit pada batas ketelitian

Arus primer pengenal

5P

10P

+/- 1% +/ -

+/- 3% +/- -

5%

10%

KelasKetelitian

o60

Page 10: Transformator Arus Current Transformator (Ct)

Kelas

Ketelitian

+ / - % Kesalahan rasio

arus % arus pengenal

5 20 100 120

+ / - pergeseran fasa

% dari arus pengenal

( menit )

5 20 100 120

0.1

0.2

0.5

1.0

0.4 0.2 0.1 0.1

0.75 0.35 0.2 0.2

1.5 0.75 0.5 0.5

3.0 1.5 1.0 1.0

15 8 5 5

30 15 10 10

90 45 30 30

180 90 60 60

KESALAHAN CT UNTUK METER

Page 11: Transformator Arus Current Transformator (Ct)

Pada arus pengenal

primer

Pada kondisi batas

ketelitian

Keslahan maksimum

Seketika %

TPX

TPY

TPZ

+/- 0.5 +/- 30

+/- 1.0 +/- 60

+/- 1.0 +/- 180 +/-

18

10

10

10

Kelas

Kesalahan kesalahan rasio sudut % menit

BATAS KESALAHAN TIPE TPX ; TPY DAN TPZ

Page 12: Transformator Arus Current Transformator (Ct)

TITIK KEJENUHAN DARI LENGKUNGMAGNITISASI ( KNEE POINT VK )

1. TITIK DIMANA BILA ARUS EKSITASI DINAIKAN 50% MAKA TEGANGAN HANYA NAIK 10 % ( BS 3938 1873 )

2. TITIK SINGGUNG GARIS DENGAN SUDUT 45 DERAJAT DENGAN KURVA TEGANGAN VERSUS ARUS EKSITASI YANG DIGAMBARKAN PADA SKALA LOG – LOG . ( ANSI )

Page 13: Transformator Arus Current Transformator (Ct)

CIRI CIRI CT UNTUK METER

# TELITI UNTUK DAERAH KERJA 5 – 120 % In# CEPAT JENUH

CIRI CT UNTUK PROTEKSI

# KELAS KETELITIAN RELATIP RENDAH PADA ARUS PENGENAL ( RATED )# KEJENUHANNYA TINGGI

Page 14: Transformator Arus Current Transformator (Ct)

PERLU DIPERHATIKAN

# SALAH SATU SISI SEKUNDER HARUS DIBUMIKAN Tujuannya kalau terjadi tembus antara tegangan tinggi dan sisi sekunder maka tegngan sisi sekunder akan naik ( merusak peralatan sisi sekunder )

# RANGKAIAN SEKUNDER TIDAK BOLEH TERBUKA Fluks akan menjadi besar - tegangan sekuder naik - terjadi kejenuhan pada inti akan panas Oleh karena itu rangkaian sekunder tidak boleh dipasang fuse / MCB .

Page 15: Transformator Arus Current Transformator (Ct)

Burden .

Adalah impedansi dari rangkaian sekunder trafo arus yang dinyatakan dalam

ohm,biasanya sering dinyatakan dalam Volt amper (VA) yang diserap pada

faktor daya tertentu dan pada arus pengenal sekunder, serta tidak mengurangi

klas ketelitiannya.

Burden CT terdiri dari impedansi kabel dan burden meter atau relai

kabel

Burden RelaiP1

P2

P1 S1

S2

Page 16: Transformator Arus Current Transformator (Ct)

1S1

1S2

WA

VAR kvarh

kWh

2S1

2S2

F 51/50 F 51/50G

Pengawatan trafo arus,

salah satu sisi sekunder di bumikan.

Page 17: Transformator Arus Current Transformator (Ct)

Tujuan salah satu sisi sekunder di bumikan.

Ialah : jika terjadi hubung singkat antara sisi primer dan sisi sekunder, tegangan sirkit sekunder tidak naik.

Pada dasarnya pembumian dapat dilakukan pada S1 atau S2 .

Dalam beberapa hal letak pembumian sisi sekunder mengikuti buku petunjuk pemasangan meter atau relainya.

Page 18: Transformator Arus Current Transformator (Ct)

1S1

1S2

WA

VAR kvarh

kWh

2S1

2S2

Tujuan sisi sekunder di hubung pendek.

Agar tidak terjadi kenaikan tegangan di sisi sekunder

Page 19: Transformator Arus Current Transformator (Ct)

PENGUJIAN TRAFO ARUS ( CT )

- PENGUJIAN RASIO CT

- PENGUJIAN LENGKUNG KEMAGNITAN ( KEJENUHAN ) CT

- PENGUJIAN R, CT.

- POLARITAS CT,

Page 20: Transformator Arus Current Transformator (Ct)

PENGUJIAN TRAFO ARUS (CT)

RANGKAIA N PENGUJIAN RASIO CT

A

220 Vac

TRAFO ISOLASISLIDE REGULATOR

ACT

P1 s1

Page 21: Transformator Arus Current Transformator (Ct)

RANGKAIA N PENGUJIAN KEJENUHAN CT

mA

220 Vac

TRAFO ISOLASISLIDE REGULATOR

A

CT

S1 P1

50 %

10%

Daerah lutut Daerah Jenuh

Daerah Lenear

I (ma)

V Volt I(ma)

Page 22: Transformator Arus Current Transformator (Ct)

Menentukan Polaritas CT.

Dengan memasukan tombol T, jika polaritas betul galvano meter G menyimpang ke kanan dan kembali ke nol,

Pada saat tombol T dilepas G menyimpang kekiri dan kemudian kembali kenol atau disebut Polaritas pengurangan

Bila salah terjadi sebaliknya.

Page 23: Transformator Arus Current Transformator (Ct)

Mengukur tahanan R. dc CT

Ω

CTP1 P2